EAxx-A Series Rotary Actuators with Integrated Electronics

The new EAxx-A series actuators with integrated microprocessor based electronics retain the reliable housing, motor and gear train of the traditional EA series. They are ideal for use with our VB-7000 or VB-9000 series of valve bodies and many other commercially available rotary shaft valve bodies with crankarms. They are used for proportional control of combustion air dampers, valves and other similar applications. Most factory assembled standard base models and options are NEMA 4 and UL/cUL listed. EA series units converted to EAxx-A series units using field retrofit kits will not be agency listed. The EAxx-A series is fully compatible with the range of valve bodies found in Section 3 of this catalog.

The Analog Input Module

The microprocessor based integral control circuit accepts current, voltage and resistance input signals. Calibration is field adjustable. Control overrides allow forcing the actuator to either end of travel on demand. Stroke lengths of 90° or 180° are switch selectable. Other stroke lengths can be set using a simple pushbutton procedure. Direction of travel is also field selectable. Default calibration is 4 to 20mA. Other ranges are switch selectable. A plug-in option board provides a 4 to 20mA position signal and two form C relays that can be set to activate at any position.

 

FEATURES:

  • Microprocessor based control
  • Switch selectable 90° or 180° stroke
  • One mA and three Vdc input ranges
  • 100 to 1000 ohm potentiometer input
  • Field configurable direction of travel and control overrides
  • Adjustable deadband, zero and span
  • Compatible wth VB series valves

 

TECHNICAL SPECIFICATIONS

Current Input: Factory set at 4 to 20mA. Span adjustable from 10 to23mA. Zero point adjustable from 0 to 6mA.
Voltage Input: 0 to 1Vdc, 1 to 5Vdc and 3 to15Vdc, switch selectable. Other ranges can be set in the configuration mode.
Resistance Input: Any potentiometer value from 100 Ohms to 1000 Ohms can be used for the input signal.
Input Impedance: mA Input: 250 Ohms
  Vdc input: >100K Ohms
Direction of Travel: Factory set to CCW with increasing signal. Can be changed in configuration mode.
Stroke Length: Factory set for 180° rotation at full scale. Can be changed to 90° by setting a switch. Other lengths can be achieved in the configuration mode.
Control Overrides: Dry contact closure can force the actuator to either end of travel.
Deadband: Adjustable from 1% to 6% of span in 0.4% increments.
Ambient Temperature: -40° to 58°C.
Humidity: 5 to 95% rh, non-condensing.
Power Requirements: See individual model numbers. Rated to operate within 10% of nominal voltage.
Option Board: 4 to 20mA position signal and two form C relays rated at 3A, resistive. The relays can be set to activate at any point within the operating range.

 

 

 

Power Connections
 EAxx-A 240V Power Connections
EAxx-A Power Connections

 

Switch Settings

 

Input Range Selection

(switches 1 through 5)

0-1 Vdc
100 to 1K Ohms
1 to 5 Vdc
Control Connections
EAxx-A Control Connections
EAxx-A Control Connections