Power Supply:
The transmitter operates on 12 to 42VDC (30VDC for I/S installations) with no load. Transmitter is protected against reverse polarity connection.
Load Limitation:
Loop resistance including optional indicator: R(k Ohms) = (Supply Voltage - 12 VDC)/(23mA)
Electromagnetic Compatability (CE Compliance):
Transmitter operates within specification in fields from 20 to 1,000MHz with field strengths to 30V/m. Meets EN 50082-1 Generic Immunity Standard and EN 55011 Compatibility Emissions Standard.
Dynamic Response:
Update Rate: 150 milliseconds (7 times per second), typical
Response to Step Change:
250 milliseconds minimum; 1 second, typical
Start-up Time:
7 sec. Operation to spec in less than 30 sec.
Ambient Temperature Change: Selfcorrecting for ambient temperature changes up to 20°C/hr.
Interchangeability:
Fully interchangeable without field calibration
Hazardous Location Certifications:
Explosion Proof: Explosion Proof Housings available with and without windows; CSA and FM approved for Class I, Div I & II, Groups B, C & D; Class II, Div I & II, Groups E, F,& G, Class III and are rated for NEMA 4X & NEMA 7 environments.
Nonincendive:
Transmitter is CSA & FM rated nonincendive in Class I, Div II, Groups A, B, C & D and Class II, Div I, Groups F & G, and Class III, Div II, CENELEC Ex N IIC T4-T6 certification pending.
Intrinsic Safety:
The Intrinsically Safe Rated Models T797-1 & T798-1 Transmitters are CSA and FM rated Intrinsically Safe for Class I, Div I, Groups A, B, C & D and Class II, Div I, Groups E, F & G, and Class III, Div I, Installed in accordance with Drawing #732-0220-00 for T797 and #732-0221-00 for T798. CENELEC EEx ia IIC T4-T6 Intrinsically Safe certification pending.
Standard Configuration:
- Sensor Input: J Type Thermocouple
- LRV (4mA): 40°F Lower Range Value
- URV (20mA): 200°F Upper Range Value
- Damping: 0 seconds
- Output Linear with Temperature
- Failsafe Upscale (23mA)