Display:
5 digit (-9999 to 99999), 3 programmable
decimal positions, red or green,
15.9mm (0.6 In.) high characters
Inputs/Outputs:
Analog Process Value (including second input)
Resolution:
<2mV for low levels, <2mV for high levels
Linearity:
Better than 0.2°C
Calibration Accuracy:
+0.2% of reading, or + 1°C or + 1LSD,
whichever is greater
User Calibration:
Low and high offsets can be applied
Input Filtering:
Off to 999.9 seconds
Thermocouples:
Types J, K, T, L, N, R, S, B and Platinel II
Cold Junction:
In automatic mode, >30 to 1 rejection of
ambient temperature change or external 0°C, 45°C, 50°C external references
3-wire Pt100: 0.3mA excitation current
Functions, 2nd analog input:
2nd process value, remote setpoint,
select min, select max., derived value
Digital Inputs: (contact closure or open collector)
Digital Inputs 1 and 2:
switching voltage/current (non-isolated
from the PV) 24VDC/20mA nominal
Triple Contact Inputs:
Specification is as per digital inputs 1 & 2,
except inputs are functionally isolated
Externally powered (triple logic inputs):
Functions:
Triple logic or contact inputs can be
configured for disable, alarm
acknowledge, keylock, remote
setpoint select, PV input 2 select,
and strain gauge 1&2 tare correction.