Eurotherm
.

DC Input, Bipolar Output Field Configurable Isolator - AP4382

Shop Online

The field configurable AP4382 isolator offers wide ranging input and output capability for scaling and transmitting analog DC signals. The AP4382 will accept input voltage spans from 10mV up to 100 volts, as well as input current spans from 1mA to 100mA. The input zero and span potentiometers enable 50% input zero and span adjustability. For example, the 0-10V input range can be elevated to 5-10V, or compressed to 0-5V. The AP4382 offers two (2) bipolar output ranges: -5 to 5V and -10 to 10V.

Model AP4382 also accepts bipolar inputs and offers selectable normal or reverse acting operation.

The AP4382 is an industrial isolator - the output is optically isolated from its input up to 1500 VDC. The ASIC-based I/O channel is independently transformer isloated from the selectable 120/240VAC power supply.

Application

The Action Pak AP4382 field configurable isolator is useful in eliminating ground loops, converting signal levels and providing signal drive. The wide ranging capability of the AP4382 provides quick universal spare part coverage.

Diagnostic LED

The AP4382 is equipped with a dual function LED signal monitor. The green, top-mounted LED indicates line power and input signal status. Active line power is indicated by an illuminated LED. If the input signal is 10% above the full scale range, the LED will flash at 8Hz. Below 0%, the flash rate is 4Hz.

Configuration

The factory preset input is 4-20mA and the output is -10 to 10V, as shown in Figure 1. The supply power is configured for 120 VAC operation. For other I/O ranges, remove the four base screws and case to access the I/O card.

WARNING: Do not change switch settings with power applied. Severe damage will result!

AP4380

FEATURES:

  • Eliminates Ground Loops

  • Field Configurable Input Ranges: 10mV to 100V, 1mA to 100mA

  • Plug-in Installation

  • Selectable 120/240VAC Power (9 to 30VDC Available)

  • ASIC Technology

 

Calibration
  1. Connect the input to a calibrated DC voltage or current source and apply power. Wait 1 hour for thermal stability before monitoring the voltage/ current output. Refer to PIN CONNECTIONS.
  2. Set the calibrator to the desired minimum input and adjust the Zero, 20-turn, potentiometer for desired minimum output.
  3. Set the calibrator to the desired maximum input and adjust the Span, 20-turn, potentiometer for desired maximum output.
  4. Repeat steps 2 and 3 for best accuracy
TECHNICAL SPECIFICATION ( AP4382)

Input     Voltage Input (field configurable)
  Full Scale Range:   10mV to 100V
  Impedance:   >100K Ohms
  Overvoltage:   400 Vrms, max (Intermittent)
      264 Vrms, max (Continous)
Current Input (field configurable)    
  Full Scale Range:   1mA to 100mA
  Impedance:   20 Ohms, typical
  Overcurrent:   170mA rms, max
  Overvoltage:   60VDC
Common Mode (Input to Ground):   1500VDC, max
Zero and Span Range    
  Zero Turn-Up:   0 to 50% of full scale range
  Span Turn-Down:   100 to 50% of full scale range
Output Voltage Output    
  Output:   -10 to 10V, -5 to 5V
  Impedance:   <10 Ohms
  Drive:   10mA, max (1K Ohms min. @ 10V)
LED Indication (green)    
  Input Range >110% input:   8Hz flash
  <0% input:   4Hz flash
Accuracy Including Linearity, Hysteresis  
  <20mV/2mA:   ±0.35% of full scale, typical, 0.5%, max
  >20mV/2mA:   ±0.1% of full scale, typical, 0.2%, max
Response Time (10-90%)   200 mSec., typical
Stability (Temperature)   ±0.025% of full scale/°C, typical,
±0.05%/°C, max
CMRR DC to 60Hz:   120dB
Isolation (Input to Output)   1500 VDC between input, output and power
ESD Susceptibility   Meets IEC 801-2, Level 2 (4KV)
Humidity (Non-Condensing)    
  Operating:   15 to 95% (@ 45°C)
  Soak:   90% for 24 hours (@ 65°C)
Temperature Range    
  Operating:   -15 to 60°C (5 to 140°F)
  Storage:   -25 to 70°C (-13 to 158°F)
Power Consumption:   3W typical, 5W max
  Standard:   selectable 120/240VAC, ±10%, 50-60Hz
  Optional:   9 to 30VDC, inverter isolated
Weight     0.60lbs
Agency Approvals   CSA certified per standard C22.2, No. M1982 (File No.LR42272-54).
      UL recognized per standard UL508 (File No. E150323).

 

Ordering Information
1. Specify: Model:   AP4382
2. Option: U, see text
3. Line Power: 120/240 VAC or 9 to 30 VDC
4. Factory calibration (C620): Specify input range, output range and power.
(All power supplies are transformer-isolated from the internal circuitry.)

 

Get a Quote

» Indicates required fields

Request for Quote
Your Details
Company Details
*Leave State / Province Code  blank if not applicable*
Contact Details
Product Requirements