Power Controllers

Our range of power controllers can drive complex and transformer coupled loads.  These products can take inputs from discrete controllers and plcs and have a wide range of full wave, half wave and phase angle firing modes to suit all load types.
   
EPower Controller The most advanced and flexible power controller.  Seven different phase configuration options - 1, 2, 3 or 4 single phase; 1 or 2 x two leg; three phase control - 3 or 4 wire star, 3 or 6 wire delta.  Current rating up to 400A.  Phase angle, half cycle, burst firing, fixed modulation and logic firing modes.  Virtually all load types.  Predictive Load Management.  Expandable I/O capability. 
TE10A Single phase.  Compact and robust design.  Analog input.  Phase angle, advanced single cycle and burst firing modes.  Current limitation.  Current rating up to 50A.
7100A Single phase.  Phase angle or fast cycle firing.  Current limit option.  Thyristor short circuit, load open and partial load failure alarms.  Also suitable for transformer burst firing.  Current ratings up to 250A.
7200A Two leg switching of three phase, three wire loads.  Current ratings up to 200A.  Diagnostic load failure analysis.  Single and burst firing modes.  Suitable for inductive loads.
7300A True three phase thyristor.  Current rating up to 160A.  Phase angle, fast cycle, single cycle, advanced single cycle and transformer burst firing modes.  Current limit option.  Digital communications.
TE200A Two leg, three phase burst firing thyristor.  Voltage, current or potentiometer inputs.  Burst and single cycle firing modes.  Current rating up to 63A.
TE300 Three phase burst firing thyristor.  Single cycle, advanced single cycle and burst firing modes.  Current rating up to 63A.
470/471/472 Single phase true power controller.  Suitable for high or low temperature coeeficient resistive loads, inductive loads or transformers.  Current rating up to 4000A (150A internal thyristors).  Phase angle, single cycle, fast cycle and slow cycle firing modes.